Using I/Os in S7–400H
13.4 Connecting redundant I/O to the PROFIBUS DP interface
S7-400H
System Manual, 03/2012, A5E00267695-11
201
The measuring error for one or two inputs shows the difference in the measurement result
depending on whether two inputs or, in case of error, only one input acquires the current of
the transmitter.
AI 8x16bit 6ES7 331–7NF00–0AB0
●
Use a 250 ohm resistor to map the current on a voltage:
Resistor
250 ohms *)
Current measuring range
+/-20 mA
4...20 mA
Input range to be parameterized
+/-5 V
1...5 V
Resolution
15 bits + sign
15 bits
S7 number format
x
Circuit-specific measuring error
- 2 parallel inputs
- 1 input
-
-
"Wire break" diagnostics
-
x
Load for 4-wire transmitters
250 ohms
Input voltage for 2-wire transmitters
> 6 V
*) It may be possible to use the freely connectable internal 250 ohm resistors of the module
AI 16x16bit 6ES7 431–7QH00–0AB0
●
Use a 50 ohm or 250 ohm resistor to map the current on a voltage:
Resistor
50 ohms
250 ohms
Current measuring range
+/-20 mA
+/-20 mA
4...20 mA
Input range to be configured
+/-1 V
+/-5 V
1...5 V
Measuring range cube position
"A"
"A"
Resolution
15 bits + sign
15 bits + sign
15 bits
S7 number format
x
x
Circuit-specific measuring error 1)
- 2 parallel inputs
- 1 input
-
-
-
-
"Wire break" diagnostics
-
-
x
Load for 4-wire transmitters
50 ohms
250 ohms
Input voltage for 2-wire transmitters
> 1.2 V
> 6 V
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...