Using I/Os in S7–400H
13.4 Connecting redundant I/O to the PROFIBUS DP interface
S7-400H
System Manual, 03/2012, A5E00267695-11
199
If the discrepancy is eliminated within the discrepancy time, analysis of the redundant input
signals is still carried out.
NOTICE
The time that the system actually needs to determine a discrepancy depends on various
factors: Bus delay times, cycle and call times in the user program, conversion times, etc.
Redundant input signals can therefore be different for a longer period than the configured
discrepancy time.
Note
There is no discrepancy analysis when a channel reports an overflow with 16#7FFF or an
underflow with 16#8000. The relevant module/channel is passivated immediately.
You should therefore disable all unused inputs in HW Config using the "Measurement type"
parameter.
Redundant analog input modules with non-redundant encoder
With non-redundant encoders, analog input modules are used in a 1-out-of-2 configuration:
5
8
,
,
$QDORJLQSXWPRGXOHV
$QDORJLQSXWPRGXOHV
$QDORJLQSXWPRGXOHV
9ROWDJHPHDVXUHPHQW
,QGLUHFWFXUUHQWPHDVXUHPHQW
'LUHFWFXUUHQWPHDVXUHPHQW
Figure 13-10 Fault-tolerant analog input modules in 1-out-of-2 configuration with one encoder
Remember the following when connecting an encoder to multiple analog input modules:
●
Connect the analog input modules in parallel for voltage sensors (left in figure).
●
You can convert a current into voltage using an external load to be able to use voltage
analog input modules connected in parallel (center in the figure).
●
2-wire transmitters are powered externally to allow you to repair the module online.
The redundancy of the fail-safe analog input modules enhances their availability.
You will find connection examples in Appendix Connection examples for redundant I/Os
(Page 461).
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...