Stand-alone operation
S7-400H
System Manual, 03/2012, A5E00267695-11
449
Fault tolerance-specific LEDs
The REDF, IFM1F, IFM2F, MSTR, RACK0 and RACK1 LEDs show the reaction specified in
the table below in stand-alone mode.
LED
Behavior
REDF
Dark
IFM1F
Dark
IFM2F
Dark
MSTR
Lit
RACK0
Lit
RACK1
Dark
Configuring stand-alone mode
Requirement: No synchronization module may be inserted in the fault-tolerant CPU.
Procedure:
1.
Insert a SIMATIC-400 station in your project.
2.
Configure the station with the fault-tolerant CPU according to your hardware
configuration. For stand-alone operation, insert the fault-tolerant CPU in a standard rack
(Insert > Station > S7–400 station in SIMATIC Manager).
3.
Parameterize the fault-tolerant CPU. Use the default values, or customize the necessary
parameters.
4.
Configure the necessary networks and connections. For stand-alone operation you can
configure "fault-tolerant S7 connections".
For help on procedure refer to the Help topics in SIMATIC Manager.
Expansion to a fault-tolerant system
WARNING
You can only expand your system to a fault-tolerant system if you have not assigned any
odd numbers to expansion units in stand-alone mode.
To expand the fault-tolerant CPU later to form a fault-tolerant system:
1.
Open a new project and insert a fault-tolerant station.
2.
Copy the entire rack from the standard SIMATIC-400 station and insert it twice into the
fault-tolerant station.
3.
Insert the subnets as required.
4.
Copy the DP slaves from the old stand-alone project to the fault-tolerant station as
required.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...