Link-up and update
12.4 Time monitoring
S7-400H
System Manual, 03/2012, A5E00267695-11
165
Calculation of the maximum communication delay
Use the following formula:
Maximum communication delay =
4 x (maximum inhibit time for priority classes > 15)
Decisive factors for determining this time are the process status and the communication load
in your system. This can be understood as the absolute load or as the load relative to the
size of your user program. You may have to adjust this time.
Calculation of the maximum cycle time extension
Use the following formula:
Maximum cycle time extension =
10 x (maximum inhibit time for priority classes > 15)
Decisive factors for determining this time are the process status and the communication load
in your system. This can be understood as the absolute load or as the load relative to the
size of your user program. You may have to adjust this time.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...