System modifications during operation
17.3 Adding components in PCS 7
S7-400H
286
System Manual, 03/2012, A5E00267695-11
17.3
Adding components in PCS 7
Starting situation
You have verified that the CPU parameters (e.g. monitoring times) match the planned new
program. Adapt the CPU parameters first, if necessary (see section Editing CPU parameters
(Page 323)).
The fault-tolerant system is operating in redundant system mode.
Procedure
Carry out the steps listed below to add hardware components to a fault-tolerant system in
PCS 7. Details of each step are described in a subsection.
Step
What has to be done?
See section
1
Modification of hardware
PCS 7, step 1: Modification of hardware
2
Offline modification of the hardware configuration
PCS 7, step 2: Offline modification of the
hardware configuration (Page 288)
3
Stopping the reserve CPU
PCS 7, step 3: Stopping the reserve CPU
4
Loading a new hardware configuration in the reserve
CPU
PCS 7, step 4: Loading a new hardware
configuration in the reserve CPU (Page 289)
5
Switching to CPU with modified configuration
PCS 7, step 5: Switch to CPU with modified
6
Transition to redundant system mode
PCS 7, step 6: Transition to redundant system
7
Editing and downloading the user program
PCS 7, step 7: Editing and downloading the user
Exceptions
This procedure for system modification does not apply in the following cases:
●
To use free channels on an existing module
●
For adding interface modules (see section Adding interface modules in PCS 7
(Page 294))
Note
After changing the hardware configuration, it is downloaded practically automatically. This
means that you no longer need to perform the steps described in sections PCS 7, step 3:
Stopping the reserve CPU (Page 288) to PCS 7, step 6: Transition to redundant system
mode (Page 291). The system behavior remains unchanged as already described.
You will find more information in the HW Config online help, "Download to module ->
Download station configuration in RUN mode".
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...