System modifications during operation
17.3 Adding components in PCS 7
S7-400H
292
System Manual, 03/2012, A5E00267695-11
17.3.7
PCS 7, step 7: Editing and downloading the user program
Starting situation
The fault-tolerant system is operating with the new hardware configuration in redundant
system mode.
CAUTION
The following program modifications are not possible in redundant system mode and result
in the system mode Stop (both CPUs in STOP mode):
Structural modifications to an FB interface or the FB instance data.
Structural modifications to global DBs.
Compression of the CFC user program.
Before the entire program is recompiled and reloaded due to such modifications the
parameter values must be read back into the CFC, otherwise the modifications to the block
parameters could be lost. You will find more detailed information on this topic in the
CFC for
S7, Continuous Function Chart manual.
Procedure
1.
Adapt the program to the new hardware configuration. You can add the following
components:
–
CFCs and SFCs
–
Blocks in existing charts
–
Connections and parameter settings
2.
Assign parameters for the added channel drivers and interconnect them with the newly
assigned icons (see section PCS 7, step 2: Offline modification of the hardware
3.
In SIMATIC Manager, select the charts folder and choose the "Options > Charts >
Generate Module Drivers" menu command.
4.
Compile only the modifications in the charts and download them to the target system.
5.
Configure the interconnections for the new CPs on both communication partners and
download them to the target system.
Result
The fault-tolerant system processes the entire system hardware with the new user program
in redundant system mode.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...