Failure and replacement of components during operation
16.2 Failure and replacement of components during operation
S7-400H
274
System Manual, 03/2012, A5E00267695-11
Procedure
The double error described results in loss of redundancy. In this event proceed as follows:
Step
What has to be done?
How does the system react?
1
Switch off one subsystem.
–
2
Replace the faulty components.
–
3
Turn the subsystem back on.
LEDs IFM1F and IFMF2F go off. The
LED MSTR of the switched on
subsystem goes out.
4
Start the CPU (for example Start from
programming device or STOP - RUN).
The CPU performs an automatic LINK-
UP and UPDATE.
The CPU changes to RUN (redundant
system mode) and operates as reserve
CPU.