Link-up and update
12.4 Time monitoring
S7-400H
162
System Manual, 03/2012, A5E00267695-11
6.
Based on your user program, determine:
–
The cycle time of the highest-priority or selected (see above) cyclic interrupt (T
WA
)
–
The execution time of your program in this cyclic interrupt (T
PROG
)
7.
For each DP master system this results in:
T
P15
(DP master system) = T
PTO
- (2 x T
TR
+ T
WA
+ T
PROG
+ T
DP_UM
+ T
SLAVE_UM
) [1]
8.
Derived for each IO subsystem:
T
P15
(IO subsystem) = T
PTO
- (2 x T
max_Akt
+ T
WA
+ T
PROG
+ T
PN_UM
+ T
Device_UM
) [1]
NOTICE
If T
P15
(DP master system) < 0 or T
P15
(IO subsystem) < 0, stop the calculation here.
Possible remedies are shown below the following example calculation. Make
appropriate changes and then restart the calculation at 1.
9.
Select the minimum of all T
P15
(DP master system) values.
This time is then known as TP15_HW.
10.
Define the share of the maximum inhibit time for I/O classes > 15 determined by the
minimum I/O retention time (T
P15_OD
):
T
P15_OD
= 50 ms + min. I/O retention time [2]
NOTICE
If T
P15_OD
> T
P15_HW
, stop the calculation here. Possible remedies are shown below the
following example calculation. Make appropriate changes and then restart the
calculation at 1.
11.
Using the information in section Performance values for link-up and update
(Page 166), calculate the share of the maximum inhibit time for priority classes > 15
defined by the user program (T
P15_AWP
).
NOTICE
If T
P15_AWP
> T
P15_HW
, stop the calculation here. Possible remedies are shown below the
following example calculation. Make appropriate changes and then restart the
calculation at 1.
12.
The recommended value for the maximum inhibit time for priority classes > 15 is now
obtained from:
T
P15 =
MAX (T
P15_AWP
, T
P15_OD
) [3]
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...