System modifications during operation
17.4 Removing components in PCS 7
S7-400H
System Manual, 03/2012, A5E00267695-11
297
17.4.2
PCS 7, step 2: Editing and downloading the user program
Starting situation
The fault-tolerant system is operating in redundant system mode.
CAUTION
The following program modifications are not possible in redundant system mode and result
in the system mode Stop (both CPUs in STOP mode):
Structural modifications to an FB interface or the FB instance data.
Structural modifications to global DBs.
Compression of the CFC user program.
Before the entire program is recompiled and reloaded due to such modifications the
parameter values must be read back into the CFC, otherwise the modifications to the block
parameters could be lost. You will find more detailed information on this topic in the
CFC for
S7, Continuous Function Chart manual.
Procedure
1.
Edit only the program elements related to the hardware removal. You can delete the
following components:
–
CFCs and SFCs
–
Blocks in existing charts
–
Channel drivers, interconnections and parameter settings
2.
In SIMATIC Manager, select the charts folder and choose the "Options > Charts >
Generate Module Drivers" menu command.
This removes the driver blocks that are no longer required.
3.
Compile only the modifications in the charts and download them to the target system.
NOTICE
Until an FC is called the first time, the value of its output is undefined. This must be
taken into account in the interconnection of the FC outputs.
Result
The fault-tolerant system continues to operate in redundant system mode. The modified user
program will no longer attempt to access the hardware being removed.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...