APPENDICES
Appendix 4 Comparison between CC-Link IE controller network and MELSECNET/H
Appendix 4.4 Precautions for system replacement
App
- 67
9
DE
DICA
T
E
D
INS
T
RUCT
IONS
10
T
R
OUB
L
E
S
HO
OT
IN
G
APPENDI
CES
INDEX
(4) Modification of station-specific parameter
The CC-Link IE controller network module does not have station-specific parameters.
Replace the setting contents of station-specific parameters with refresh parameters of
the CC-Link IE controller network module.
(Example of replacement)
The following shows the example of replacement when changing the network range
assignment as shown below with station-specific parameters.
1) Move device of station No.1 (b). (B100 to B1FF
B500 to B5FF)
2) Close up devices of station No.2 to No.5.
(To the next page)
Figure App.1 Setting example of station-specific parameter
Figure App.2 Assignment with station-specific parameter
Station No.1(a)
Station No.2
Station No.3
Station No.4
Station No.5
Station No.1(b)
Link relay (B)
Link refresh
Link refresh
CPU module
0
FF
100
1FF
200
2FF
300
3FF
400
4FF
500
5FF
Station No.1(a)
Station No.2
Station No.3
Station No.4
Station No.5
Station No.1(b)
Station-specific parameter (LB)
MELSECNET/H module
0
FF
100
1FF
200
2FF
300
3FF
400
4FF
500
5FF
Station No.1(a)
Station No.1(b)
Station No.2
Station No.3
Station No.4
Station No.5
Network range assignment (LB)
0
1FF
200
2FF
300
3FF
400
4FF
500
5FF