6.3 Network Range Assignment
6.3.1 LB/LW settings
6
PARAMETER SETTING
(2) Using equal assignment
The link device range can be equally assigned to each send range of the relevant
stations.
(a) Clicking
in [Assignment the CC IE Control network range] will display
the [Equal assignment] dialog box.
Set the following items and click
.
(Example) When assigning a LB range of 0 to 7FF (2048 points) equally to the
send ranges of stations 1 to 4
(b) Equal assignment is done in [LB/LW settings (1)] of [Assignment the CC IE
Control network range].
Figure 6.4 [Equal assignment] dialog box
Table 6.9 Setting items in the [Equal assignment] dialog box
Item
Description
Assignment target
Select [LB/LW settings (1)] or [LB/LW settings (2)].
B/W equal
assignment
Start station
Set the start station.
(Setting range for Universal model QCPU: 1 to 120, Default: None)
(Setting range for other than Universal model QCPU: 1 to 64, Default: None)
End station
Set the end station.
(Setting range for Universal model QCPU: 1 to 120, Default: None)
(Setting range for other than Universal model QCPU: 1 to 64, Default: None)
Start No.
Set the start number of the LB/LW for equal assignment.
• LB (Setting range: 0000
H
to 7FF0
H
, Default: None)
• LW (Setting range: 0000
H
to 1FFFF
H
, Default: None)
Total points
assigned
Set the total points of LB/LW, which are to be assigned equally.
• LB (Setting range: 16 to 32768, Default: None)
• LW (Setting range: 1 to 131072, Default: None)