APPENDICES
Appendix 2 Link Special Register (SW) List
App
- 23
9
DE
DICA
T
E
D
INS
T
RUCT
IONS
10
T
R
OUB
L
E
S
HO
OT
IN
G
APPENDI
CES
INDEX
SW0060
Maximum link scan time
Stores the maximum value of link scan time at cyclic transmission. (Unit: ms)
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error is held.
SW0061
Minimum link scan time
Stores the minimum value of link scan time at cyclic transmission. (Unit: ms)
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error is held.
SW0062
Current link scan time
Stores the current value of link scan time at cyclic transmission.
The stored value includes an error of up to 1ms. (Unit: ms)
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error is held.
SW0063
Communication mode
Stores the setting value of the constant link scan which is set by
supplementary setting.
0: No setting
1 to 500: Setting value of constant link scan (Unit: ms)
(Condition)
• Valid when Data link status of own station (SB0049) is OFF.
SW0064
Own station's loop
status
Stores the transmission path status of the own station.
00
H
: Normal
12
H
: IN-side loopback (OUT-side cable disconnection)
13
H
: IN-side loopback (OUT-side cable insertion error)
14
H
: IN-side loopback (OUT-side line establishing)
21
H
: OUT-side loopback (IN-side cable disconnection)
31
H
: OUT-side loopback (IN-side cable insertion error)
41
H
: OUT-side loopback (IN-side line establishing)
22
H
: Disconnecting (IN-side or OUT-side cable disconnection)
23
H
: Disconnecting (IN-side cable disconnection, OUT-side cable insertion
error)
24
H
: Disconnecting (IN-side cable disconnection, OUT-side line
establishing)
32
H
: Disconnecting (IN-side cable insertion error, OUT-side cable
disconnection)
33
H
: Disconnecting (IN-side or OUT-side cable insertion error)
34
H
: Disconnecting (IN-side cable insertion error, OUT-side line
establishing)
42
H
: Disconnecting (IN-side line establishing, OUT-side cable
disconnection)
43
H
: Disconnecting (IN-side line establishing, OUT-side cable insertion
error)
44
H
: Disconnecting (IN-side or OUT-side line establishing)
Table App.4 Link special register (SW) list (Continued)
No.
Name
Description