9
DEDICATED INSTRUCTIONS
9.5 JP/GP.WRITE
9
- 33
9
DE
DICA
T
E
D
INS
T
RUCT
IONS
10
T
R
OUB
L
E
S
HO
OT
IN
G
APPENDI
CES
INDEX
(S1)+1
Completion status
The instruction completion status is stored.
0: Normal
Other than 0: Error (
—
System
(S1)+2
Channel used by
own station
*2
Specify the channel used by the own station. (
When executing multiple link dedicated instructions at the same time)
1 to 10
(1 to 8 when the
own station is a
safety CPU)
User
(S1)+3
Target station's
CPU type
Specify the type of the target station CPU.
0000
H
03D0
H
to 03D3
H
03E0
H
to 03E3
H
03FF
H
User
Setting value
Description
0000
H
Target station CPU, control CPU, own system
CPU
(Specified data are the same as "03FF
H
".)
03D0
H
Control system CPU
03D1
H
Standby system CPU
03D2
H
System A CPU
03D3
H
System B CPU
03E0
H
• Target station CPU (single CPU system)
• Multi-CPU No.1
03E1
H
Multi-CPU No.2
03E2
H
Multi-CPU No.3
03E3
H
Multi-CPU No.4
03FF
H
Target station CPU, control CPU, own system
CPU
When the instruction is executed with control system CPU (03D0
H
) or
standby system CPU (03D1
H
) specified, if system switching occurs at
the target station, the instruction execution may fail. (Error code:
4244
H
, 4248
H
)
If the instruction has failed with the above error, execute it again.
(S1)+4
Target station
network No.
Specify the network No. of the target station.
1 to 239: Network No.
254: Specify this when 254 has been set in Jn.
1 to 239
254
User
Table 9.17 Control data (Continued)
Device
Item
Setting data
Setting range
Setting
side
*1