9
- 120
9.13 J(P).ZNWR
9
DEDICATED INSTRUCTIONS
(2) Function
(a) ZNWR instruction overview
The ZNWR instruction writes word device data (in and after (S1)) of the own
station to word devices of the target station (in and after (D1)).
The target station is specified in Target station network No. (Jn) and Target station
No. (n1).
Upon completion of writing data to the target station devices, Completion device
(D2) turns ON.
For concurrent execution of multiple link dedicated instructions, refer to the
following.
Section 9.2.2 (1) When executing multiple link dedicated instructions at the
(b) Target stations available for specification
1) Target network
In addition to CC-Link IE controller network, stations in the following networks
can be also specified.
• MELSECNET/H
• MELSECNET/10
• Ethernet
2) Target station's CPU type
The ZNWR instruction is executable when the target station has Q/QnA/
AnUCPU.
Figure 9.102 ZNWR instruction
Channel 2
(Fixed)
ZNWR
CC-Link IE controller
network module
CPU module
CPU module
Network module
(S1)
(D1)
[Own station]
[Target station]