6.3 Network Range Assignment
6
PARAMETER SETTING
6.3
Network Range Assignment
To the control station, assign each station's send range required for cyclic transmission
and configure supplementary settings for data communication.
POINT
Network range assignments are set to the control station only.
Normal stations perform cyclic transmission according to the range assigned at
the control station.
1) Select [CC IE Control (Control station)] for [Network type] in the [Setting the
number of Ethernet/CC IE/MELSECNET cards] dialog box.
2) Clicking
will display the [Assignment the CC IE
Control network range] dialog box.
Refer to the following explanation to make settings.
Figure 6.2 [Assignment the CC IE Control network range] dialog box
Table 6.7 Setting items in [Assignment the CC IE Control network range] dialog box
Item
Description
System switching
monitoring time
Set a length of time that will be taken from a data link stop (Data link status (SB0049)
turns ON) until issue of a system switching request in units of 10ms.
(Setting range: 10 to 5000ms, Default: 2000ms)
Data link monitoring time
Set the time for monitoring the link scan time in units of 5ms.
Normally, it is recommended to use the default value.
If the link scan time exceeds the monitoring time, data linking is disabled.
(Setting range: 5 to 2000ms, Default: 2000ms)
Total slave stations
Displays the total number of stations in the network.
Parameter name
Set a name for parameters as required.
(Up to eight characters)
Switch screens
Select a desired setting screen.
LB/LW settings (1)
Set each station's send range in LB/LW to use it for communication by LB/LW.
(
LB/LW settings (2)