9
- 84
9.9 JP/GP.SEND
9
DEDICATED INSTRUCTIONS
* 1 The setting side is as shown below.
User: Before execution of the link dedicated instruction, data must be set by the user.
System: The CPU module stores the execution result of the link dedicated instruction.
* 2 Data are stored only when 1 is set in bit 7 of Error completion type ((S1)+0).
* 3 Logical channel setting is not available for the CC-Link IE controller network module.
(
Appendix 4.2 (1) Comparison of function with MELSECNET/H)
(S1)+9
Send data length
Specify the send data size of (S2) to (S2)+n.
When the target station is QCPU: 1 to 960 words
When the target station is QnACPU: 1 to 480 words
When the target station has a QCPU, check the version of the
network module on the target station.
The size of receive data is restricted depending on the version.
(
Manual for the network module on the target station)
1 to 960
User
(S1)+10
—
Unused
0
User
(S1)+11
Clock set flag
*2
The valid or invalid status of the data in the area starting from (S1)+12
is stored.
0: Invalid
1: Valid
—
System
(S1)+12
to
(S1)+15
Clock data on error
completion
*2
Clock data on error completion are stored in BCD format.
When the target station is QnACPU, "00
H
" is stored in the Year field
(first two digits of the year).
—
System
(S1)+16
Error-detected
network No.
*2
Network No. of the station, where an error was detected, is stored.
(However, when an error is detected at the own station, the network
No. is not stored.)
1 to 239: Network No.
—
System
(S1)+17
Error-detected
station No.
*2
Station No. of the station, where an error was detected, is stored.
(However, when an error is detected at the own station, the network
No. is not stored.)
1 to 120: Station No.
—
System
Table 9.48 Control data (Continued)
Device
Item
Setting data
Setting range
Setting
side
*1
(S1)+12
(S1)+13
(S1)+14
(S1)+15
Month (01
H
to 12
H
)
Hour (00
H
to 23
H
)
Second (00
H
to 59
H
)
Day (01
H
to 31
H
)
Minute (00
H
to 59
H
)
00
H
(Sun.) to 06
H
(Sat.)
Day of week (00
H
to 06
H
)
Year (00
H
to 99
H
), First 2 digits
Year (00
H
to 99
H
), Last 2 digits
b15
b8 b7
to
b0
to