DEDICATED INSTRUCTIONS
9.12 J(P).ZNRD
9
- 111
9
DE
DICA
T
E
D
INS
T
RUCT
IONS
10
T
R
OUB
L
E
S
HO
OT
IN
G
APPENDI
CES
INDEX
(2) Function
(a) ZNRD instruction overview
The ZNRD instruction reads out word device data (in and after (S1)) of the target
station into word devices of the own station (in and after (D1)).
The target station is specified in Target station network No. (Jn) and Target station
No. (n1).
Upon completion of reading the target station devices, Completion device (D2)
turns ON.
For concurrent execution of multiple link dedicated instructions, refer to the
following.
Section 9.2.2 (1) When executing multiple link dedicated instructions at the
(b) Target stations available for specification
1) Target network
In addition to CC-Link IE controller network, stations in the following networks
can be also specified.
• MELSECNET/H
• MELSECNET/10
• Ethernet
2) Target station's CPU type
The ZNRD instruction is executable when the target station has Q/QnA/
AnUCPU.
Figure 9.92 ZNRD instruction
Channel 1
(Fixed)
ZNRD
CC-Link IE controller
network module
CPU module
CPU module
Network module
(D1)
(S1)
[Own station]
[Target station]