The following is an example of performing the self-loopback test on the CC-Link IE
controller network module of system B.
Set the operation mode of the redundant system to separate mode for the
self-loopback test.
(a) System configuration
1) Connect GX Developer to the control system CPU.
2) Turn OFF the power and connect an optical fiber cable to OUT and IN of the
CC-Link IE controller network module of system B.
3) Turn ON the power.
(b) Change the operation mode of the redundant system to separate mode.
In the Redundant operation window of GX Developer, select [Change operation
mode] and [Separate mode] and execute it.
Figure 5.16 System configuration
Figure 5.17 Redundant operation in GX Developer
GX Developer
System A (control system)
Control station
No.1
System B (standby system)
Normal station