9
- 172
9.19 J(P)/G(P).RIRD
9
DEDICATED INSTRUCTIONS
(6) Program example
In this program example, when M200 turns ON, data in D1000 to D1004 of station
No.4 (target station) are read out to D800 to D804 of station No.1 (own station).
(a) System configuration example
(b) Devices used in the program example
1) Link special relay (SB) and link special register (SW)
Remark
For details of link special relay (SB) and link special register (SW), refer to the
following.
• Appendix 1 Link Special Relay (SB) List
• Appendix 2 Link Special Register (SW) List
2) Devices used by the user
Figure 9.149 System configuration example
Table 9.105 Link special relay (SB) and link special register (SW)
Device
Description
Device
Description
SB0047
Baton pass status (own station)
SW00A0.3
Baton pass status of station No.4
Table 9.106 Devices used by the user
Device
Description
Device
Description
M200
Start contact
D400 to
D404
Control data
M201
RIRD executing flag
D624
Error code storage device
M205
Completion device
D800 to
D804
Read data storage device (station No.1)
M206
Completion status indication device
—
D800
D801
D802
D803
D804
D1000
D1001
D1002
D1003
D1004
Network No.1
Station No.1
CPU module
CC-Link IE
controller
network
module
Station No.2
Station No.4
Station No.3
CPU module
CC-Link IE
controller
network
module
CPU module
CC-Link IE
controller
network
module
CPU module
CC-Link IE
controller
network
module
RIRD instruction
request source
(Own station)
RIRD instruction
request target
(Target station)
Receive
buffer
Содержание QJ71GP21-SX
Страница 1: ......
Страница 2: ......
Страница 644: ...App 94 Appendix 6 External Dimensions Appendix 6 2 QJ71GP21S SX APPENDICES Memo ...
Страница 649: ......
Страница 650: ......