10.1 Troubleshooting Flow
10.1.6 Cyclic transmission is disabled
10
- 7
9
DE
DICA
T
E
D
INS
T
RUCT
IONS
10
T
R
OUB
L
E
S
HO
OT
IN
G
APPENDI
CES
INDEX
10
TROUBLESHOOTING
10.1.6
Cyclic transmission is disabled
The following flowchart shows the procedures to be taken when cyclic transmission is
disabled.
Figure 10.7 When cyclic transmission is disabled
Cyclic transmission is disabled.
Yes
Yes
OFF/flashing
Is D LINK LED of own or
another station turned ON?
ON
No
Is the same shared group
as for the own station set when
the group cyclic transmission
function is used?
Does the station have a
CPU other than Basic model
QCPU or safety CPU?
In "Network range assignment" of the control station,
check the shared group.
No
Stations of Basic model QCPUs or safety CPUs
cannot receive other stations' data set in the area
of LB/LW 4000 or higher.
Assign the data required for them within the range
of LB/LW 0 to 3FFF.
1)
Section 10.1.4 D LINK LED is OFF