TROUBLESHOOTING
4) Present Control and Assign Control
Present Control: Displayed to the station actually operating as control station.
Assign Control: Displayed to the station set by network parameters.
POINT
(1) When multiple stations on the same system (in a multiple CPU system
configuration) have the same network No.
If a station other than those on the system is selected while a station of the
lowest start I/O No. has a baton pass error, a transient execution error (no
baton passing on the own station) (E504
H
) will occur.
Resolve the baton pass error, and then redo the operation.