6.2 Network Setting
6
PARAMETER SETTING
(1) Network type
Select the station type of the CC-Link IE controller network module.
For a Basic model QCPU or safety CPU, it is fixed to "CC IE Control (Normal station)".
(2) Starting I/O No.
Set the start I/O number of the CC-Link IE controller network module in 16-point units.
(Setting range: 0000
H
to 0FE0
H
, Default: None)
(3) Network No.
Set a network No. of the network to which the CC-Link IE controller network module is
connected. (Setting range: 1 to 239, Default: None)
POINT
When multiple network modules and/or Ethernet modules are mounted for one
programmable controller, set different network Nos. for them.
(4) Total stations
When [CC IE Control (Control station)] is selected in [Network type], set the total
number of stations in one network.
(Setting range for Universal model QCPU: 2 to 120, Default: None)
(Setting range for other than Universal model QCPU: 2 to 64, Default: None)
(5) Group No.
Set a group No. for performing transient transmission by group specification.
(Setting range: 1 to 32, Default: 0 (No group specification))
Refer to the following for transient transmission by group specification.
Table 6.4 Selection items of [Network type]
Item
Description
CC IE Control (Control
station)
Set this for the CC-Link IE controller network control station.
(One control station is needed for a single network.)
CC IE Control (Normal
station)
Set this for the CC-Link IE controller network normal station.