9.7 J(P)/G(P).REQ (Remote RUN/STOP)
9
DEDICATED INSTRUCTIONS
* 1 The setting side is as shown below.
User: Before execution of the link dedicated instruction, data must be set by the user.
System: The CPU module stores the execution result of the link dedicated instruction.
* 2 Data are valid only when 1 is set in bit 7 of Error completion type ((S1)+0).
(b) Request data (All set by the user)
: Set —: Not set
(S1)+16
Error-detected
network No.
*2
Network No. of the station, where an error was detected, is stored.
(However, when an error is detected at the own station, the network
No. is not stored.)
1 to 239: Network No.
—
System
(S1)+17
Error-detected
station No.
*2
Station No. of the station, where an error was detected, is stored.
(However, when an error is detected at the own station, the station
No. is not stored.)
1 to 120: Station No.
—
System
Table 9.27 Request data
Device
Item
Setting data
Remote RUN
Remote STOP
(S2)+0
Request type
0010
H
: When station No. is specified in (S1)+5
0030
H
: When all stations or a group is specified in (S1)+5
(S2)+1
Sub-request type
0001
H
: Remote RUN
0002
H
: Remote STOP
(S2)+2
Operation mode
Specify whether to forcibly execute remote RUN/STOP or not.
The forced execution is a function that forces a station which has
stopped by remote STOP to RUN remotely from another station.
• For remote RUN
0001
H
: No forced execution
0003
H
: Forced execution
• For remote STOP
0003
H
(Fixed)
(S2)+3
Clear mode
Specify the CPU module device status for the case of remote RUN.
0000
H
: Do not clear
(Note that the local devices are cleared.)
0001
H
: Clear (excluding the latch range)
0002
H
: Clear (including the latch range)
Clear mode ((S2)+3) allows specification of the CPU module device
clear (initialization) process at the start of CPU module operation
activated by remote RUN.
The CPU module will perform the specified clear processing, and
then it will run according to the setting that can be confirmed by [PLC
parameters] - [PLC file] - [Initial Device value] in GX Developer.
—
Table 9.26 Control data (Continued)
Device
Item
Setting data
Setting range
Setting
side
*1