(2) Control data
* 1 The setting side is as shown below.
User: Before execution of the link dedicated instruction, data must be set by the user.
System: The CPU module stores the execution result of the link dedicated instruction.
POINT
The UINI instruction can be executed only once.
Once a station No. has been set up, the UINI instruction cannot be executed
again. (Doing so will result in error completion.)
In the case of error completion of the UINI instruction, however, take corrective
actions against the error and execute the UINI instruction again.
(3) Function
(a) UINI instruction overview
This instruction sets the station No. of the normal station (own station) that is
specified in Un.
Upon completion of the station No. setting, Completion device (D1) turns ON.
Table 9.97 Control data
Device
Item
Setting data
Setting range
Setting
side
*1
(S1)+0
—
Unused
0
User
(S1)+1
Completion status
The instruction completion status is stored.
0: Normal
Other than 0: Error (
—
System
(S1)+2
Modification
specification
Specify the modification.
0001
H
: Station No. setting
0001
H
User
(S1)+3
Own station No.
Specify a station No. of the own station.
1 to 120
User
(S1)+4 to
(S1)+9
—
Unused
0
User
Figure 9.139 UINI instruction
255 2
Station No.
(SW0042)
UINI
CC-Link IE controller
network module
CPU module
(S1)
[Own station]