9
- 156
9.17 Z(P).RTMWR
9
DEDICATED INSTRUCTIONS
(3) Function
(a) RTMWR instruction overview
This instruction is used to write clock data to a programmable controller on
another station.
The target station is specified in Target station network No. (Jn) and Target station
No. (n2).
Upon completion of the request to the target station, the completion device (D2)
turns ON.
(b) Target stations available for specification
1) Target network
In addition to CC-Link IE controller network, stations in the following networks
can be also specified.
• MELSECNET/H
• MELSECNET/10
• Ethernet
2) Target station's CPU type
The RTMWR instruction is executable only when the target station has QCPU.
Figure 9.132 RTMWR instruction
Channel 1
Channel n
Clock data
Channel 8
RTMWR
CC-Link IE controller
network module
CPU module
CPU module
Network module
(D1)
[Own station]
[Target station]
Содержание QJ71GP21-SX
Страница 1: ......
Страница 2: ......
Страница 644: ...App 94 Appendix 6 External Dimensions Appendix 6 2 QJ71GP21S SX APPENDICES Memo ...
Страница 649: ......
Страница 650: ......