APPENDICES
Appendix 1 Link Special Relay (SB) List
App
- 9
9
DE
DICA
T
E
D
INS
T
RUCT
IONS
10
T
R
OUB
L
E
S
HO
OT
IN
G
APPENDI
CES
INDEX
SB006B
Own station's OUT-side
cabling status
Stores the OUT-side cabling status of own station.
OFF: Normal
ON: Inserted incorrectly
SB006C
Own station's IN-side
error frame reception
status
Stores whether the error frame is received or not in the IN-side of own station.
OFF: Error frame is not received at present
ON: Error frame is received at present
SB006D
Own station's OUT-side
error frame reception
status
Stores whether the error frame is received or not in the OUT-side of own
station.
OFF: Error frame is not received at present
ON: Error frame is received at present
SB006E
Own station's IN-side
error frame detection
Stores whether the error frame is received or not in the IN-side of the own
station from power-on to the present.
OFF: Error frame not received
ON: Error frame received
SB006F
Own station's OUT-side
error frame detection
Stores whether the error frame is received or not in the OUT-side of the own
station from power-on to the present.
OFF: Error frame not received
ON: Error frame received
SB0070
Station No. setting
status (own station)
Stores the station No. setting status of the own station when using the UINI
instruction for station No. setting.
OFF: Station No. determined
ON: Station No. not yet determined
A determined station No. of the own station can be confirmed in Station No.
(SW0042).
SB008E
Path switching
detection flag
Stores the path switching detection status.
OFF: Path switching not detected
ON: Path switching detected
The stored value is cleared when Clear loop switch count (SB0009) is turned
ON.
SB008F
Transient error
Stores the transient transmission error detection status.
OFF: Error not detected
ON: Error detected
When an error is detected, the number of errors can be checked in Transient
transmission error (SW006F).
SB0090
Hardware test
completion status
Stores the completion status of hardware test.
OFF: Not executed or being executed
ON : Completed
When completed, the completion status can be checked in Hardware test
normal/error completion status (SB0091).
SB0091
Hardware test normal/
error completion status
Stores the normal or error completion status of the hardware test.
OFF: Completed normally
ON : Failed
(Condition)
• Valid when Hardware test completion status (SB0090) is ON.
SB0092
Self-loopback test
completion status
Stores the completion status of the self-loopback test.
OFF: Not executed or being executed
ON : Completed
When completed, the completion status can be checked in Self-loopback test
normal/error completion status (SB0093).
Table App.2 Link special relay (SB) list (Continued)
No.
Name
Description
Availability
Control
station
Normal
station
Link special relay (SB): SB006B to SB0092
Содержание QJ71GP21-SX
Страница 1: ......
Страница 2: ......
Страница 644: ...App 94 Appendix 6 External Dimensions Appendix 6 2 QJ71GP21S SX APPENDICES Memo ...
Страница 649: ......
Страница 650: ......