9
DEDICATED INSTRUCTIONS
9.3 JP/GP. READ
9
- 19
9
DE
DICA
T
E
D
INS
T
RUCT
IONS
10
T
R
OUB
L
E
S
HO
OT
IN
G
APPENDI
CES
INDEX
2) Devices used by the user
(c) READ instruction settings
Control data settings for the READ instruction are shown below.
Table 9.10 Devices used by the user
Device
Description
Device
Description
M100
Control data setting command
D200 to
D217
Control data
M101
Start contact
D600
Error code storage device
M105
Completion device
D700 to
D704
Read data storage device (station No.1)
M106
Completion status indication device
—
Table 9.11 READ instruction settings
Device
Item
Set value
(S1)+0
D200
Error completion type
0081
H
(Clock data at the time of error
completion is set.)
(S1)+1
D201
Completion status
—
(Set by the system, no setting required)
(S1)+2
D202
Channel used by own station
1
(S1)+3
D203
Target station's CPU type
0000
H
(Target station CPU)
(S1)+4
D204
Target station network No.
1
(S1)+5
D205
Target station No.
4
(S1)+6
D206
(Unused)
0
(S1)+7
D207
Number of resends
5 times
(S1)+8
D208
Arrival monitoring time
0 (10 seconds)
(S1)+9
D209
Read data length
5 words
(S1)+10
D210
(Unused)
0
(S1)+11
D211
Clock set flag
—
(Set by the system, no setting required)
(S1)+12
to
(S1)+15
D212 to D215
Clock data on error
completion
(S1)+16
D216
Error-detected network No.
(S1)+17
D217
Error-detected station No.