6
- 23
6.3 Network Range Assignment
6.3.3 Shared group
6
PARAMETER SETTING
(4) Precautions
(a) Do not perform the shared group setting for any station of a Universal model
QCPU that does not support the group cyclic transmission function and stations
other than Universal model QCPUs.
If it is set by mistake, cyclic data of the stations in different shared groups will not
refreshed to the devices of the CPU module.
(b) In [Supplementary settings], enable [Block data assurance per station]. (Default)
Section 6.3.6 Supplementary settings
If [Block data assurance per station] is disabled, cyclic data of the stations in
different shared groups will not be refreshed to the devices of the CPU module.
Remark
It is recommended to refresh cyclic data of the stations with no shared group
setting and the stations of the same shared group No. as of the own station.
Cyclic data of the stations in different shared groups need not be refreshed.
Section 6.4 Refresh Parameters
The following is an example of refresh parameter setting for station No.4 in the
system given in (3) in this section
Figure 6.17 Refresh parameters for station No.4
W0 to W3FF
W400 to W4FF
W500 to W5FF
LW0 to LW3FF
LW400 to LW4FF
LW500 to LW5FF
LW600 to LW6FF
LW700 to LW7FF
LW1FFFF
CPU module
Link register (W)
CC-Link IE controller
network module (station No.4)
Link register (LW)
No.1
No.1
No.4
No.5
No.5
No.2
No.3
No.4 send range