4
FUNCTIONS
4.5 Station No. Setting by Sequence Program
4
- 57
1
O
V
ER
VI
E
W
2
SYST
EM
CO
NF
IG
URA
T
IO
N
3
SPECI
F
IC
A
T
IO
N
S
4
F
UNCT
IONS
5
PREP
ARA
T
IO
N AND
SET
UP
6
P
A
RAM
E
T
E
R
SET
TI
NG
7
PRO
C
ESSI
NG
T
IM
E
8
PRO
G
R
AM
M
ING
(1) Using the UINI instruction (
Set a station No. of a normal station (own station) with the UINI instruction.
(2) Setting up Network parameters
For use of the UINI instruction, select "Specify station No. by program." in Network
parameters.
(3) Precautions
For a multiple CPU system consisting of Universal model QCPU(s) and any other
model QCPU(s), set station No. of the CC-Link IE controller network module by a
network parameter.
In such a case, if the station No. of the CC-Link IE controller network module is set by
the UINI instruction, access to other than Universal model QCPUs via the CC-Link IE
controller network module is not available.
Figure 4.64 Station No. setting using UINI instruction
Figure 4.65 Precautions for multiple CPU system
ZR0
Station
No.2
No station
No. specified
Project data
CPU module
CC-Link IE controller
network module
Parameter
Parameter
Sequence program
Sequence program
Network parameter
(Specify station No. by program.)
M0
M0V H1 D102
ZP.UINI "U0" D100 M5
M1 SB70 (Station No. setting status (own station))
M0V ZR0 D103
2
Save station No. in a latch-set device or file register.
At power-on, system starts up with no station No. specified.
When executing the UINI instruction, set the station No. according to control data.
After station No. setting with the UINI instruction, cyclic and transient transmissions start.
GX Developer
Universal model QCPU
High Performance model QCPU
CC-Link IE controller network module
(Station No. set by program)
1
2
1
2
1
2
Control CPU setting
UINI
Not accessible to other
than Universal model
QCPU.
Содержание QJ71GP21-SX
Страница 1: ......
Страница 2: ......
Страница 644: ...App 94 Appendix 6 External Dimensions Appendix 6 2 QJ71GP21S SX APPENDICES Memo ...
Страница 649: ......
Страница 650: ......