9
DEDICATED INSTRUCTIONS
9.9 JP/GP.SEND
9
- 83
9
DE
DICA
T
E
D
INS
T
RUCT
IONS
10
T
R
OUB
L
E
S
HO
OT
IN
G
APPENDI
CES
INDEX
(S1)+1
Completion status
The instruction completion status is stored.
0: Normal
Other than 0: Error (
—
System
(S1)+2
Channel used by
own station
Specify the channel used by the own station.
(
Section 9.2.2 (2) When executing a link dedicated instruction
1 to 8
User
(S1)+3
Target station
channel
Specify a channel of the target station for storing data.
*3
1 to 8
User
(S1)+4
Target station
network No.
Specify the network No. of the target station.
1 to 239: Network No.
254: Specify this when 254 has been set in Jn.
1 to 239
254
User
(S1)+5
Target station No.
Specify the station No. of the target station.
(1) Station No. specification
When own station is Universal model QCPU: 1 to 120
When own station is other than Universal model QCPUs: 1 to 64
To increase the reliability of data, it is recommended to execute
the instruction with the Execution/Error completion type ((S1)+0)
set to "1: With arrival confirmation".
(2) Group
81
H
to A0
H
: All stations in group No.1 to 32
(Setting is available when the execution type is set to "0: With
arrival confirmation" in (S1)+0.)
(3) All stations
FF
H
: All stations of the target network No. (Except the own
station)
(Setting is available when the execution type is set to "0: No
arrival confirmation" in (S1)+0.)
1 to 120
81
H
to A0
H
FF
H
User
(S1)+6
—
Unused
0
User
(S1)+7
Number of resends
1) For instruction execution
Specify the number of times the instruction is to be resent when
it is not completed within the monitoring time specified in (S1)+8.
(Setting is valid when the execution type is set to "1: With arrival
confirmation" in (S1)+0.)
0 to 15
User
2) At instruction completion
The number of resends executed (result) is stored. (Setting is
valid when the execution type is set to "1: With arrival
confirmation" in (S1)+0.)
—
System
(S1)+8
Arrival monitoring
time
Specify the monitoring time required for instruction completion.
(Setting is available when the execution type is set to "1: With arrival
confirmation" in (S1)+0.)
If an instruction is not completed within this time, it will be resent the
number of times specified in (S1)+7.
0: 10 seconds
1 to 32767: 1 to 32767 seconds
0 to 32767
User
Table 9.48 Control data (Continued)
Device
Item
Setting data
Setting range
Setting
side
*1
Group No.1 … 81
H
Group No.2 … 82
H
Group No.32 … A0
H