APPENDICES
Appendix 1 Link Special Relay (SB) List
App
- 3
9
DE
DICA
T
E
D
INS
T
RUCT
IONS
10
T
R
OUB
L
E
S
HO
OT
IN
G
APPENDI
CES
INDEX
SB0008
Clear OUT-side
transmission error count
Clears the OUT-side line error detection area (SB006F, SB0150, SW006A,
SW006B, SW0084, SW0150 to SW0157) into 0.
OFF: Clear not directed
ON : Clear directed (Number of errors is not counted during ON)
SB0009
Clear loop switch count
Clears the own station's path switching detection area (SB008E, SB0160,
SW006E, SW0160 to SW0167) and path switching history (Un\G2784 to 2945)
to 0.
OFF: Clear not directed
ON: Clear directed (The number of switching is not counted during ON)
SB000A
Clear transient
transmission errors
Clears the own station's area for transient transmission errors (SB008F,
SB0170, SW006F, SW170 to SW0177) and transient transmission error log
(Un\2592 to 2753) to 0.
OFF: Clear not directed
ON: Clear directed (Number of errors is not counted during ON)
SB000C
Normal connection
information refresh
instruction
Updates the normal connection information of the own station.
OFF: No refresh instruction
ON: Refresh instructed (valid at rising)
If executed with the conditions for normal connection information acquisition
not satisfied, the normal connection information is cleared.
(
Section 10.3.1 (3) Display position of a disconnected station)
SB0017
Data-link-error-induced
system switching
disable flag
Disables system switching due to a data link error.
OFF: Enable (System switching is requested to the control system CPU.)
ON: Disable (System switching is not requested to the control system CPU.)
SB0020
Module status
Stores the CC-Link IE controller network module status.
OFF: Normal
ON: Error
SB0030
RECV execution
request flag (1)
Stores the data reception status of channel 1 of the own station.
OFF: No data reception
ON: Data received
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error are held.
SB0031
RECV execution
request flag (2)
Stores the data reception status of channel 2 of the own station.
OFF: No data reception
ON: Data received
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error are held.
SB0032
RECV execution
request flag (3)
Stores the data reception status of channel 3 of the own station.
OFF: No data reception
ON: Data received
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error are held.
Table App.2 Link special relay (SB) list (Continued)
No.
Name
Description
Availability
Control
station
Normal
station
Link special relay (SB): SB0008 to SB0032
Содержание QJ71GP21-SX
Страница 1: ......
Страница 2: ......
Страница 644: ...App 94 Appendix 6 External Dimensions Appendix 6 2 QJ71GP21S SX APPENDICES Memo ...
Страница 649: ......
Страница 650: ......