DEDICATED INSTRUCTIONS
9.14 Z(P).RRUN
9
- 129
9
DE
DICA
T
E
D
INS
T
RUCT
IONS
10
T
R
OUB
L
E
S
HO
OT
IN
G
APPENDI
CES
INDEX
* 1 Local devices and file registers for each program cannot be used as devices in setting data.
POINT
(1) Remote RUN is available when the RUN/STOP switch of the target station
CPU is set to "RUN".
(2) Remote RUN is not executable when system protect is applied to the target
station CPU.
(3) When the target station CPU has been already in remote STOP/PAUSE state
by a request from another station, it cannot enter RUN mode if Mode (n4) is
"No forced execution (0001
H
)".
n4
Mode
Specify options for the operation mode and clear mode.
Binary 16 bits
1) Operation mode
Specify whether to forcibly execute remote RUN or not.
1
H
: No forced execution
3
H
: Forced execution
The forced execution is a function that forces a station, which has
stopped by remote STOP, to RUN remotely from another station.
2) Clear mode
Specify the CPU module device status for the case of remote
RUN.
0
H
: Do not clear
(Note that the local devices are cleared.)
1
H
: Clear (excluding the latch range)
2
H
: Clear (including the latch range)
Clear mode allows specification of the CPU module device clear
(initialization) process at the start of CPU module operation activated
by remote RUN.
The CPU module will perform the specified clear processing, and then
it will run according to the setting that can be confirmed by [PLC
parameters] - [PLC file] - [Initial Device value] in GX Developer.
(D1)
The own station's device that is turned on for one scan upon
completion of the instruction
(D1)+1 also turns ON if the instruction execution has failed.
Bit
Table 9.74 Setting data(Continued)
Setting data
*1
Description
Data type
b15
to
0
2)
1)
to
b8 b7
to
b4 b3
b0