(2) Setting network parameters in GX Developer
(a) Set the control station to Circuit test mode.
After setting the following network parameters in GX Developer, write them to the
programmable controller.
POINT
p
When a network contains a redundant system, pairing settings are required for
network parameters of the control station.
Select the control station's [Network range assignment] - [Pairing] to configure the
settings.
(b) Setting the normal station to Online mode
After setting the following network parameters in GX Developer, write them to the
programmable controller.
Figure 5.26 Network parameters in GX Developer
Table 5.9 Network parameter setting items of GX Developer
Item
Set value
Network type
CC IE Control (Control station)
Starting I/O No.
0000
Network No.
1
Total stations
4
Group No.
0
Station No.
1
Mode
Circuit test
Figure 5.27 Network parameters in GX Developer
Table 5.10 Network parameter setting items of GX Developer
Item
Set value
Network type
CC IE Control (Normal station)
Starting I/O No.
0000
Network No.
1
Group No.
0
Station No.
2 to 4
Mode
On line