9
- 82
9.9 JP/GP.SEND
9
DEDICATED INSTRUCTIONS
(2) Control data
Table 9.48 Control data
Device
Item
Setting data
Setting range
Setting
side
*1
(S1)+0
Execution/Error
completion type
0000
H
0001
H
0080
H
0081
H
User
1) Execution type (bit 0)
0: No arrival confirmation
When the target station is on the same network
Completed when data are sent from the own station.
When the target station is on another network
Completed when data reach a relay station on the same network.
1: With arrival confirmation
Completed when data are stored in the specified channel area of
the target station.
When "0: No arrival confirmation" is specified, even if transmission to
the target station is terminated abnormally in the following cases, it is
normal completion on the own station.
•Communication itself was completed normally, although the data
sent were erroneous.
•Data could not be stored in the target station because instructions
from multiple stations were sent to the same station. (An error code
(E006
H
or E205
H
) is detected on the target station.)
2) Error completion type (bit 7)
Specify the clock data setup status for error completion.
0: Clock data at the time of error completion is not set in the area
starting from (S1)+11.
1: Clock data at the time of error completion is set in the area
starting from (S1)+11.
b15
0
0
2)
1)
b7
b0
to
to
Completed
Target
station
Request
source
Completed
Relay
station
Target
station
Request
source
Completed
Completed
Relay
station
Target
station
Target
station
Request
source