10.2 Error Code List
10
TROUBLESHOOTING
E122
H
Duplicated station No. (UINI
instruction)
Duplicated station No. was set for
the own station using the UINI
instruction.
• Change the own station No. setting in the control
data, and then retry the instruction.
• Change the other station's No. which is
duplicated.
E123
H
Station No. already set (UINI
instruction)
After setting a station No. with the
UINI instruction, the instruction was
executed again.
• Station No. setting with the UINI instruction is
limited to one time only.
Reset the CPU module, and then retry the
instruction.
E130
H
Pairing setting error
Pairing is not set for the station of a
Redundant CPU.
• Check the pairing setting in "Network range
assignment" of the control station.
E131
H
Pairing setting error
Pairing is set for a station other than
Redundant CPUs.
E152
H
Link startup condition error
Link startup was attempted from a
station different from the one where
cyclic transmission has stopped.
• Execute link startup from the station where
cyclic transmission has stopped.
• Execute the forced link startup.
E160
H
Invalid link startup/stop
direction
The link stop/startup direction
content (SW0000) was not set
properly.
• Check the setting and stop or restart cyclic
transmission.
E162
H
Link startup/stop reexecution
error (instructed by other
station)
Reexecution was attempted during
processing for cyclic transmission
stop/restart.
• Reexecute it after completing the processing for
cyclic transmission stop/restart.
E163
H
Link startup/stop reexecution
error (instructed by own
station)
E164
H
Link startup/stop reexecution
error (instructed by entire
system)
E165
H
Link startup/stop station
specification error
The link stop/startup direction
contents (SW0001 to SW0008) were
not set properly.
• Check the setting and stop or restart cyclic
transmission.
E166
H
Link startup/stop group
specification error
The link stop/startup group
specification (SW0012 to SW0013)
is not correct.
E170
H
to
E172
H
Network module error
The hardware has failed.
• Please consult your local Mitsubishi
representative.
E173
H
Communication test retry error
During execution of the
communication test, the test was
retried.
• Reexecute it after completing the currently
executing communication test.
E174
H
Communication test
transmission completion signal
retried out
The maximum number of
transmission completion signal
retries was reached.
• Check the network status in the CC IE Control
Network Diagnostics, and retry the operation.
• Check if the routing parameters are set correctly.
E175
H
Communication test
monitoring time timeout
No response has been returned
within the communication monitoring
time.
E176
H
Communication test
transmission completion wait
time timed out
Timeout has occurred without
transmission completion.
E177
H
to
E179
H
Network module error
The hardware has failed.
• Please consult your local Mitsubishi
representative.
E17A
H
Duplicated communication test
data reception
The response data have been
received two times or more.
• Check the network status in the CC IE Control
Network Diagnostics, and retry the operation.
E17B
H
Network module error
The hardware has failed.
• Please consult your local Mitsubishi
representative.
Table 10.1 Error Code List (Continued)
Error code
Error
Error detail
Corrective action