2) Devices used by the user
(c) REQ instruction (Remote RUN/STOP) settings
Settings for the REQ instruction (remote RUN/STOP) are shown below.
1) Control data
2) Request data
Table 9.30 Devices used by the user
Device
Description
Device
Description
M120
Control and request data setting command
D240 to
D257
Control data
M121
Start contact
D260 to
D263
Request data
M125
Completion device
D265 to
D266
Response data
M126
Completion status indication device
D604
Error code storage device
Table 9.31 Control data for the REQ instruction
Device
Item
Set value
(S1)+0
D240
Error completion type
0091
H
(Clock data at the time of error
completion is set.)
(S1)+1
D241
Completion status
—
(Set by the system, no setting required)
(S1)+2
D242
Channel used by own station
3
(S1)+3
D243
Target station's CPU type
0000
H
(Target station CPU)
(S1)+4
D244
Target station network No.
1
(S1)+5
D245
Target station No.
2
(S1)+6
D246
(Unused)
0
(S1)+7
D247
Number of resends
5 times
(S1)+8
D248
Arrival monitoring time
0 (10 seconds)
(S1)+9
D249
Request data length
3 (Remote STOP)
(S1)+10
D250
Response data length
—
(Set by the system, no setting required)
(S1)+11
D251
Clock set flag
(S1)+12
to
(S1)+15
D252 to D255
Clock data on error completion
(S1)+16
D256
Error-detected network No.
(S1)+17
D257
Error-detected station No.
Table 9.32 Request data of the REQ instruction
Device
Item
Set value
(S2)+0
D260
Request type
0010
H
(When station No. is specified in
(S1)+5)
(S2)+1
D261
Sub-request type
0002
H
(Remote STOP)
(S2)+2
D262
Operation mode
0003
H
(Forced execution)
(S2)+3
D263
Clear mode
(Setting is not required for remote STOP.)