5.6 Tests for CC-Link IE controller network Startup
5.6.2 Station-to-station test
5
PREPARATION AND SETUP
(2) System configuration and parameter setting for a redundant system
The following is an example of setting the CC-Link IE controller network module of
system B to the executing station.
Set the operation mode of the redundant system to separate mode for the
station-to-station test.
(a) System configuration
1) Connect GX Developer to the control system CPU.
2) Turn OFF the power and connect an optical fiber cable between OUT of the
executing station and IN of the other station.
3) Turn ON the power.
(b) Change the operation mode of the redundant system to separate mode.
In the Redundant operation window of GX Developer, select [Change operation
mode] and [Separate mode] and execute it.
Figure 5.33 System configuration
Figure 5.34 Redundant operation in GX Developer
GX Developer
System A (control system)
Control station
No.1
Station-to-station test
(executing station)
System B (standby system)
Normal station
No.2
Tracking cable
Station-to-station test
(target station)
Normal station
No.3