10.2 Error Code List
10
- 17
9
DE
DICA
T
E
D
INS
T
RUCT
IONS
10
T
R
OUB
L
E
S
HO
OT
IN
G
APPENDI
CES
INDEX
10
TROUBLESHOOTING
E17C
H
Communication test target
station specification error
The own station or a relay station
was selected as a destination.
• Confirm a correct destination and retry the
operation.
E200
H
Network module error
The hardware has failed.
• Please consult your local Mitsubishi
representative.
E201
H
Duplicated transient data
reception error
The same transient data have been
received two times or more.
• Check the network status in the CC IE Control
Network Diagnostics, and retry the operation.
E202
H
Network module error
The hardware has failed.
• Please consult your local Mitsubishi
representative.
E203
H
Send buffer full
The send buffer is full.
• Temporarily stop the transient transmission, and
then retry it.
• Reduce the operation frequency of transient
transmission, and then retry the operation.
• Using the COM instruction, increase the
processing frequency of transient transmission.
(
Section 9.2.1 Precautions for Dedicated
• If the error persists even after taking the above
actions, please consult your local Mitsubishi
representative.
E204
H
Transient data resend count
exceeded
The specified number of resends has
been reached.
• Check the network status in the CC IE Control
Network Diagnostics.
E205
H
Receive buffer full
The receive buffer is full.
• Temporarily stop the transient transmission, and
then retry it.
• Reduce the operation frequency of transient
transmission and retry the operation.
• Using the COM instruction, increase the
processing frequency of transient transmission.
(
Section 9.2.1 Precautions for Dedicated
• If the error persists even after taking the above
actions, please consult your local Mitsubishi
representative.
E206
H
Network module error
The hardware has failed.
• Please consult your local Mitsubishi
representative.
E207
H
Transient data receiving
network No. error
Although the data are sent and
received within the same network,
network numbers of the own and
target stations are different.
• Check the network numbers of the own and
target stations in Network parameters, and
execute it again.
E208
H
Transient data target station
No. error
The target station No. setting is not
correct.
• Confirm the target station No. on the own
station, and retry the operation.
• If the error persists even after taking the above
action, please consult your local Mitsubishi
representative.
E209
H
Network module error
The hardware has failed.
• Please consult your local Mitsubishi
representative.
E20A
H
E20B
H
Transient data relay count
error
The number of relay stations
exceeded seven.
• Modify the system configuration so that the
number of relay stations is seven or less.
• Check if the routing parameters are set correctly.
E20C
H
to
E20E
H
Network module error
The hardware has failed.
• Please consult your local Mitsubishi
representative.
Table 10.1 Error Code List (Continued)