6
- 1
6.1 Parameter List
6
PARAMETER SETTING
CHAPTER6 PARAMETER SETTING
This chapter describes the parameters of the CC-Link IE controller network module.
6.1
Parameter List
This list shows the CC-Link IE controller network module parameters.
(1) Parameter list for the control station
Table 6.1 Parameter list for the control station
1)Safety CPU
2)Basic model QCPU
3)High Performance model QCPU
4)Process CPU
5)Redundant CPU
6)Universal model QCPU
Item
Description
CPU module
Reference
section
1)
2)
3)
4)
5)
6)
Network
setting
Network type
Select the station type of the CC-Link IE controller
network module.
Starting I/O No.
Set the start I/O number of the CC-Link IE controller
network module in 16-point units.
Network No.
Set a network No. of the network to which the
CC-Link IE controller network module is connected.
Total stations
Set the total number of stations in one network.
Group No.
Set a group No. for performing transient transmission
by group specification.
*1
*1
*1
*1
Station No.
Set a station No. of the CC-Link IE controller network
module.
Mode
Select an operation mode of the CC-Link IE
controller network module.
Station No. setting
method
For Universal model QCPUs, select how to set
station Nos. of normal stations.
Network
range
assignment
System switching
monitoring time
Set a length of time that will be taken from a data link
stop (Data link status of own station (SB0049) turns
ON) until issue of a system switching request in units
of 10ms.
*1
*1
*1
*1
Data link monitoring
time
Set the time for monitoring the link scan time in units
of 5ms.
*1
*1
*1
*1
LB/LW settings (1)
Set each station's send range in LB/LW to use it for
communication by LB/LW.
LB/LW settings (2)
LX/LY settings (1)
For each block, set an I/O master station and I/O
ranges used in the LX/LY communication between
the I/O master and relevant stations.
LX/LY settings (2)
Specify I/O master
station
Shared group
For a Universal model QCPU, set stations that will
share their cyclic data to the same Shared group No.
Pairing
If the network contains a redundant system, set a
combination of stations of system A and system B.
Specify reserved
station
Set reserved station(s).
Supplementary
setting
Set the constant link scan time, block data assurance
per station, punctuality assurance, and the maximum
number of transient transmissions for one station.
*1
*1
*1
*1