3
- 4
3.2 Function Lists
3
SPECIFICATIONS
(2) List of transient transmission functions
: Available, : Partially available, : N/A
* 1 Station No.65 or higher cannot be specified as a target station.
* 2 Writing from another station to a safety CPU is not allowed.
* 3 For the read/write data length, 961 words or more cannot be specified.
Channel 9 or 10 cannot be specified as a channel used by the own station.
* 4 If the request source is a safety CPU, other stations are not accessible.
* 5 Station No.65 or higher cannot be specified as a relay target station.
Table 3.3 List of transient transmission functions
1)Safety CPU
2)Basic model QCPU
3)High Performance model QCPU
4)Process CPU
5)Redundant CPU
6)Universal model QCPU
Function
Description
CPU module
Reference
section
1)
2)
3)
4)
5)
6)
Link dedicated
instruction
Read from/write to
other station devices
(for Q/QnA series)
Reads or writes data from or to devices of a
programmable controller on another station.
(READ/SREAD/WRITE/SWRITE instruction)
*1
*2
*3
*1
*1
*1
*1
Transient request to
another station (for Q/
QnA series)
Remotely runs or stops a programmable controller
on another station. (REQ instruction)
*1
*1
*1
*1
Reads or writes clock data from or to a
programmable controller on another station. (REQ
instruction)
*1
*2
*1
*1
*1
*1
Data send/receive (for
Q/QnA series)
Sends data to a programmable controller on another
station. (SEND instruction)
Reads data received from a programmable controller
on another station. (RECV/RECVS instruction)
*1
*1
*1
*1
Read from/write to
other station devices
(For A series)
Reads or writes data from or to devices of a
programmable controller on another station.
(ZNRD/ZNWR instruction)
Remote RUN/STOP
(For Q series)
Remotely run or stop a programmable controller on
another station. (RRUN/RSTOP instruction)
*1
*1
*1
*1
Read/write of another
station's clock data
(For Q series)
Reads or writes clock data from or to a
programmable controller on another station.
(RTMRD/RTMWR instruction)
*1
*2
*1
*1
*1
*1
CC-Link
dedicated
instruction
Read/write of another
station's data
Reads or writes the specified points of data from the
target station's device. (RIRD/RIWT instruction)
GX Developer access to other stations
Using GX Developer allows seamless access to the
Ethernet, CC-Link IE controller network,
MELSECNET/H, MELSECNET/10, and CC-Link
systems.
*1
*4
*1
*1
*1
*1
Group
By specifying transient transmission target stations
as a group, data can be sent to all stations of the
same group No.
Routing
Allows transient transmissions to stations located on
other networks in a multi-network system.
*5
*5
*5
*5
*5
Clock setting from GX Developer
In GX Developer, the clock of the CPU module that is
connected to the network can be set up.
Changing No. of transient
transmissions
The number of transient transmissions that one
station can execute during one link scan can be
changed.