9
- 70
9.8 J(P)/G(P).REQ (Reading/Writing Clock Data)
9
DEDICATED INSTRUCTIONS
(c) Response data (All set by the user)
When "all stations or a group (FF
H
or 81
H
to A0
H
)" is specified in Target station
No. ((S1)+5), no response data will be stored.
: Stored —: Not stored
POINT
Clock data cannot be written when system protect is applied to the target station
CPU.
Table 9.37 Response data
Device
Item
Setting data
Clock data
read
Clock data
write
(D1)+0
Request type
0081
H
: Clock data read
0091
H
: Clock data write (when station No. is specified in (S1)+5)
(D1)+1
Sub-request
type
0002
H
: Clock data read
0001
H
: Clock data write
(D1)+2
Clock data read
Clock data that have been read are stored as BCD codes.
—
(D1)+3
—
(D1)+4
—
(D1)+5
—
(D1)+2
(D1)+3
(D1)+4
(D1)+5
Month (01
H
to 12
H
)
Hour (00
H
to 23
H
)
Second (00
H
to 59
H
)
Day (01
H
to 31
H
)
Minute (00
H
to 59
H
)
00
H
(Sun.) to 06
H
(Sat.)
Day of week (00
H
to 06
H
)
00
H
Year (00
H
to 99
H
) Last 2 digits
b15
b8 b7
to
b0
to