9.11 Z.RECVS
9
DEDICATED INSTRUCTIONS
(2) Control data
* 1 The setting side is as shown below.
User: Before execution of the link dedicated instruction, data must be set by the user.
System: The CPU module stores the execution result of the link dedicated instruction.
(3) Function
(a) RECVS instruction overview
Data sent by the SEND instruction from another station are read out from the
specified channel to the word devices (in and after (D1)) on the own station.
Table 9.61 Control data
Device
Item
Setting data
Setting range
Setting
side
*1
(S1)+0
Execution Error
completion type
0000
H
User
(S1)+1
Completion status
The instruction completion status is stored.
0: Normal
Other than 0: Error (
—
System
(S1)+2
Own station
channel
Specify the channel of the own station, where receive data are stored.
(
Section 9.2.2 (1) When executing multiple link dedicated
instructions at the same time)
1 to 8
User
(S1)+3
Channel used by
sending station
Stores the channel used by the sending station.
1 to 8: Channel
—
System
(S1)+4
Network No. of
sending station
Stores network No. of the sending station.
1 to 239: Network No.
—
System
(S1)+5
Sending station
No.
Stores station No. of the sending station.
1 to 120: Station No.
—
System
(S1)+6
—
Unused
0
User
(S1)+7
—
Unused
0
User
(S1)+8
—
Unused
0
User
(S1)+9
Receive data
length
Stores the receive data size stored in (D1) to (D2)+n.
1 to 960: Receive data size (words)
—
System
Figure 9.83 RECVS instruction
b15
0000
H
(Fixed)
b0
to
Channel 1
Channel n
Channel 8
Channel 1
Channel n
Channel 8
RECVS
Writing by
SEND
CC-Link IE controller
network module
CPU module
CPU module
Network module
(D1)
[Own station]
[Sending station]