8.3 Using Link Special Relay (SB) and Link Special Register (SW)
8
PROGRAMMING
(b) Cyclic transmission stop/restart of own station
(Cyclic transmission stop)
1) Turn Link stop (own station) (SB0001) ON.
2) When the CC-Link IE controller network module accepts a request, Cyclic
transmission stop accept status (own station) (SB004E) is turned ON.
3) When the cyclic transmission stop is completed, Cyclic transmission stop
completion status (own station) (SB004F) is turned ON.
4) If the cyclic transmission stop is completed abnormally, an error code will be
stored in Data linking stop status (own station) (SW004F).
5) Turn Link stop (own station) (SB0001) OFF.
(Cyclic transmission restart)
6) Turn Link startup (own station) (SB0000) ON.
7) When the CC-Link IE controller network module accepts the request, Cyclic
transmission start accept status (own station) (SB004C) is turned ON.
8) When the cyclic transmission restart is completed, Cyclic transmission start
completion status (own station) (SB004D) is turned ON.
9) If the cyclic transmission restart is completed abnormally, an error code will be
stored in Data linking start status (own station) (SW004D).
10)Turn Link startup (own station) (SB0000) OFF.
Table 8.12 SB/SW used in cyclic transmission stop/restart of own station
No.
Description
No.
Description
SB0000
Link startup (own station)
—
SB0001
Link stop (own station)
SB004C
Cyclic transmission start accept status (own station)
SB004D
Cyclic transmission start completion status (own
station)
SW004D
Data linking start status (own station)
SB004E
Cyclic transmission stop accept status (own station)
—
SB004F
Cyclic transmission stop completion status (own
station)
SW004F
Data linking stop status (own station)