9
- 168
9.19 J(P)/G(P).RIRD
9
DEDICATED INSTRUCTIONS
(2) Control data
(a) Control data
* 1 The setting side is as shown below.
User: Before execution of the dedicated instruction, data must be set by the user.
System: The CPU module stores the execution result of the dedicated instruction.
(b) Access code/Attribute code
* 1 Devices other than the above are not accessible.
For access to a bit device, specify 0 or multiples of 16.
* 2 When the target station is other than the CC-Link IE controller network module, refer to the manual
for the target station for the access and attribute codes.
Table 9.103 Control data
Device
Item
Setting data
Setting range
Setting
side *1
(S)+0
Completion status
The instruction completion status is stored.
0: Normal
Other than 0: Error (
When the target station is other than the CC-Link IE controller
network module, refer to the manual for the target station for error
codes.
—
System
(S)+1
Target station No.
Specify the station No. of the target station.
1 to 120
User
(S)+2
Access code/
Attribute code
Specify an access code and an attribute code of the read target
device.
Refer to (b)
User
(S)+3
Device No.
Specify the start No. of the read target device.
Within device range
User
(S)+4
Number of points
to read
Specify the size of the data to be read in units of words.
1 to 480
User
Table 9.104 Access code/Attribute code
Device contents
*1
Name
Device type
Unit
Access code
*2
Attribute code
*2
Bit
Word
Input relay
X
Hexadecimal
01
H
05
H
Output relay
Y
Hexadecimal
02
H
Internal relay
M
Decimal
03
H
Latch relay
L
Decimal
83
H
Link relay
B
Hexadecimal
23
H
Timer (contact)
T
Decimal
09
H
Timer (coil)
T
Decimal
0A
H
Timer (present value)
T
Decimal
0C
H
Retentive timer (contact)
ST
Decimal
89
H
Retentive timer (coil)
ST
Decimal
8A
H
Retentive timer (present value)
ST
Decimal
8C
H
Counter (contact)
C
Decimal
11
H
Counter (coil)
C
Decimal
12
H
Counter (present value)
C
Decimal
14
H
Data register
*3
D
Decimal
04
H
Link register
*3
W
Hexadecimal
24
H
File register
R
Decimal
84
H
Link special relay
SB
Hexadecimal
63
H
Link special register
SW
Hexadecimal
64
H
Special relay
SM
Decimal
43
H
Special register
SD
Decimal
44
H
Access code
b15
b8 b7
b0
to
to
Attribute code
Содержание QJ71GP21-SX