8
- 51
8.3 Using Link Special Relay (SB) and Link Special Register (SW)
8
PROGRAMMING
(b) Checking parameter status of own station
1) When receiving parameters is completed, Parameter receive status (SB0054)
is turned OFF.
2) When parameters have an error, Received parameter error (SB0055) is turned
ON and an error code is stored in Parameter setting status (SW0055).
3) The presence or absence of parameters can be checked with Parameter
information (SW0054).
4) When the parameters are reflected in the CC-Link IE controller network
module, contents of parameters are stored in the following link special relay
(SB) and link special register (SW).
Table 8.30 SB/SW used in checking reflection status of parameters of own station
No.
Description
No.
Description
SB0054
Parameter receive status
SW0054
Parameter information
SB0055
Received parameter error
SW0055
Parameter setting status
Table 8.31 SB/SW used in checking parameters of own station
No.
Description
No.
Description
SB0040
Network type (own station)
SW0040
Network No.
—
SW0041
Group No.
SW0042
Station No.
SB0043
Online switch (own station)
SW0043
Mode status
SB0044
Station setting (own station)
SW0044
Station setting
—
SW0046
Module type
SB0048
Control station status (own station)
—
—
SW004C
Shared group No.
SB0056
Communication status
SW0056
Current control station
—
SW0057
Designated control station
SW0059
Total number of link stations
SB005C
I/O master station (Block 1)
SW005C
I/O master station (Block 1)
SB005D
I/O master station (Block 2)
SW005D
I/O master station (Block 2)
SB005E
Own station's CPU type
—
SB0060
Communication mode
SW0063
Communication mode
SB0061
Cyclic transmission punctuality assurance
—
SB00C0
Reserved station specification
SW00C0 to
SW00C7
Reserved station specification
Содержание QJ71GP21-SX
Страница 1: ......
Страница 2: ......
Страница 644: ...App 94 Appendix 6 External Dimensions Appendix 6 2 QJ71GP21S SX APPENDICES Memo ...
Страница 649: ......
Страница 650: ......