10.2 Error Code List
10
- 15
9
DE
DICA
T
E
D
INS
T
RUCT
IONS
10
T
R
OUB
L
E
S
HO
OT
IN
G
APPENDI
CES
INDEX
10
TROUBLESHOOTING
E01C
H
Network module error
The hardware has failed.
• Please consult your local Mitsubishi
representative.
E101
H
Parameter error
Some of the network parameters is
incorrect.
• Write correct network parameters to the
programmable controller.
• If the error persists even after taking the above
action, please consult your local Mitsubishi
representative.
E102
H
Reserved own station error
The own station was set as a
reserved station.
• Cancel the reserved station setting in "Network
range assignment" of the control station.
• Change the station No. to the one that is not
specified as a reserved station.
E103
H
Invalid own station No.
The own station No. set is outside
the range of total stations.
• Increase the number of total stations in the
network setting of the control station.
• Change the station number to the one that is
within the number of total stations.
E104
H
to
E10A
H
Parameter error
Some of the network parameters is
incorrect.
• Write correct network parameters to the
programmable controller.
• If the error persists even after taking the above
action, please consult your local Mitsubishi
representative.
E10B
H
Parameter error
The CPU module or CC-Link IE
controller network module does not
support the added function.
• Use a CPU module or CC-Link IE controller
network module that supports the added
function.
Appendix 3 Functional Upgrade of
• If the error persists even after taking the above
action, please consult your local Mitsubishi
representative.
E10C
H
E10D
H
Network module error
The hardware has failed.
• Please consult your local Mitsubishi
representative.
E110
H
to
E117
H
Parameter error
Some of the network parameters is
incorrect.
• Write correct network parameters to the
programmable controller.
• If the error persists even after taking the above
action, please consult your local Mitsubishi
representative.
E11A
H
Start device No. error (LW)
The Basic model QCPU or safety
CPU's own send range is set to LB/
LW4000 or higher.
• Check "LB/LW settings (1)" in "Network range
assignment" of the control station.
E11B
H
Start device No. error (LB)
E11C
H
LB/LW settings (2) error (LW)
The Basic model QCPU or safety
CPU's own send range is set in "LB/
LW settings (2)".
• Check "LB/LW settings (2)" in "Network range
assignment" of the control station.
E11D
H
LB/LW settings (2) error (LB)
E11E
H
End device No. error (LW)
The Basic model QCPU or safety
CPU's own send range is set to LB/
LW4000 or higher.
• Check "LB/LW settings (1)" in "Network range
assignment" of the control station.
E11F
H
End device No. error (LB)
E120
H
UINI execution at control
station
The UINI instruction was executed at
a control station.
• Setting the station number with the UINI
instruction is not allowed for control stations.
Set it with a network parameter.
• Change the station type setting to Normal
station, and then retry it.
E121
H
Own station No. error (UINI
instruction)
With "Specify station No. by
parameter." selected in Network
parameters, the UINI instruction was
executed.
• Select "Specify station No. by program." in
Network parameters, and execute it again.
Table 10.1 Error Code List (Continued)
Error code
Error
Error detail
Corrective action