APPENDICES
Appendix 4 Comparison between CC-Link IE controller network and MELSECNET/H
Appendix 4.3 Link special relays (SB) and link special registers (SW)
App
- 63
9
DE
DICA
T
E
D
INS
T
RUCT
IONS
10
T
R
OUB
L
E
S
HO
OT
IN
G
APPENDI
CES
INDEX
SW00C9
Number of retries on the
reverse loop side
SW006A
SW006B
OUT-side line error
occurrence rate (Max.)
OUT-side line error
occurrence rate (present.)
(Content
changed)
• This operation in the
MELSECNET/H can be
substituted by OUT-side line
error occurrence rate in the
CC-Link IE controller
network module.
• The station No. for the
station that receives an error
frame at OUT-side can be
checked by SW0130 to
SW0137 and SW0150 to
SW0157.
SW00CC
Line error on the forward loop
side
SW0068
SW0069
IN-side line error occurrence
rate (Max.)
IN-side line error occurrence
rate (present.)
(Content
changed)
• This operation in the
MELSECNET/H can be
substituted by IN-side line
error occurrence rate in the
CC-Link IE controller
network module.
• The station No. for the
station that receives an error
frame at IN-side can be
checked by SW0120 to
SW0127 and SW0140 to
SW0147.
SW00CD
Line error on the reverse loop
side
SW006A
SW006B
OUT-side line error
occurrence rate (Max.)
OUT-side line error
occurrence rate (present.)
(Content
changed)
• This operation in the
MELSECNET/H can be
substituted by OUT-side line
error occurrence rate in the
CC-Link IE controller
network module.
• The station No. for the
station that receives an error
frame at OUT-side can be
checked by SW0130 to
SW0137 and SW0150 to
SW0157.
SW00CE
Number of loop switches
SW006E
Number of loop switches
(No. changed)
None
SW00CF
Loop switch data pointer
—
—
—
Delete the sequence program
for the corresponding part.
SW00D0 to
SW00DF
Loop switch data
SW0064
SW0065
Own station's loop status
Loopback information
(Content
changed)
• The cause of loopback can
be checked by Own station's
loop status (SW0064).
• The loop status of a network
can be checked by
Loopback information
(SW0065).
SW00E0 to
SW00E7
Switch request station
—
—
—
Delete the sequence program
for the corresponding part.
SW00E8 to
SW00EB
Module type of each station
—
—
SW00EC
Low-speed cyclic transmission
start execution results
—
—
Table App.26 Comparison of link special register (SW) (Continued)
MELSECNET/H
CC-Link IE controller network
Compatibility
Precautions for replacement
No.
Name
No.
Name
Содержание QJ71GP21-SX