10
- 14
10.2 Error Code List
10
TROUBLESHOOTING
10.2 Error Code List
The list of error codes is shown below.
Error codes can be confirmed by the following.
• "System monitor" in GX Developer (
Section 10.3.4 System monitor)
• Completion status in the control data of a dedicated instruction.
(
CHAPTER 9 DEDICATED INSTRUCTIONS)
Table 10.1 Error Code List
Error code
Error
Error detail
Corrective action
4000
H
to
4FFF
H
Errors detected by the CPU module
Troubleshooting in the QCPU User's Manual (Hardware Design, Maintenance and Inspection)
7000
H
to
7FFF
H
Errors detected by the serial communication module, etc.
Troubleshooting in the Serial Communication Module User's Manual
B000
H
to
BFFF
H
Errors detected by the CC-Link system
Troubleshooting in the CC-Link System Master/Local Module User's Manual
C000
H
to
CFFF
H
Errors detected by the Ethernet interface module
Troubleshooting in the Ethernet Interface Module User's Manual
E000
H
to
E005
H
Network module error
The hardware has failed.
• Please consult your local Mitsubishi
representative.
E006
H
Receive queue full
The receive queue is full.
• Temporarily stop the transient transmission, and
then retry it.
• Reduce the operation frequency of transient
transmission, and then retry the operation.
• Using the COM instruction, increase the
processing frequency of transient transmission.
(
Section 9.2.1 Precautions for Dedicated
• If the error persists even after taking the above
actions, please consult your local Mitsubishi
representative.
E007
H
to
E011
H
Network module error
The hardware has failed.
• Please consult your local Mitsubishi
representative.
E012
H
Parameter check result error
The network parameter setting is not
correct.
• Write correct network parameters to the
programmable controller.
• If the error persists even after taking the above
action, please consult your local Mitsubishi
representative.
E013
H
E014
H
to
E018
H
Network module error
The hardware has failed.
• Please consult your local Mitsubishi
representative.
E019
H
CPU module error
No response has been received from
the CPU for 5 seconds.
E01A
H
CPU module stop error
A stop error has occurred in the CPU
module.
• Check the error in "PLC diagnostics" of GX
Developer, and take corrective actions.
E01B
H
CPU module power failure
Power failure occurred in the CPU
module.
• The CPU module has been powered off.
Power it on again.
Содержание QJ71GP21-SX
Страница 1: ......
Страница 2: ......
Страница 644: ...App 94 Appendix 6 External Dimensions Appendix 6 2 QJ71GP21S SX APPENDICES Memo ...
Страница 649: ......
Страница 650: ......