9
DEDICATED INSTRUCTIONS
9.19 J(P)/G(P).RIRD
9
- 167
9
DE
DICA
T
E
D
INS
T
RUCT
IONS
10
T
R
OUB
L
E
S
HO
OT
IN
G
APPENDI
CES
INDEX
9.19 J(P)/G(P).RIRD
This instruction is used to read the specified points of data from the target station device.
(1) Setting data
* 1 Local devices and file registers for each program cannot be used as devices used in setting data.
Table 9.101 Devices available for setting data
Setting
data
Available devices
Internal device
(System, User)
File
register
Link direct device
J
\
Intelligent
function
module device
U
\
G
Index
register Zn
Constant
Others
Bit
Word
Bit
Word
K,H
$
(S)
—
—
(D1)
—
—
(D2)
—
Figure 9.144 Instruction format
Table 9.102 Setting data
Setting data
*1
Description
Data type
Jn
Network number of the own station (1 to 239, 254)
254: The network specified in Valid module during other station access
Binary 16 bits
Un
Start I/O number of the own station's CC-Link IE controller network
module
(00 to FE
H
: The higher two digits of the 3-digit I/O number)
(S)
Start device of the own station that stores control data.
(
(2) Control data in this section)
Device name
(D1)
The own station's start device where readout data will be stored
(D2)
The own station's device that is turned on for one scan upon
completion of the instruction.
(D2) + 1 also turns on if the instruction execution has failed.
Bit
J.RIRD
Start contact
[Instruction format]
[Execution
condition]
[Instruction
symbol]
JP.RIRD
Start contact
J.RIRD
Jn
(S)
(D1)
(D2)
Jn
(S)
(D1)
(D2)
Un
(S)
(D1)
(D2)
Un
(S)
(D1)
(D2)
JP.RIRD
G.RIRD
Start contact
GP.RIRD
Start contact
G.RIRD
GP.RIRD