9
- 34
9.5 JP/GP.WRITE
9
DEDICATED INSTRUCTIONS
(S1)+5
Target station No.
Specify the station No. of the target station.
(1) Station No. specification
When own station is Universal model QCPU: 1 to 120
When own station is other than Universal model QCPUs: 1 to 64
To increase the reliability of data, it is recommended to execute
the instruction with the Execution/Error completion type ((S1)+0)
set to "1: With arrival confirmation".
(2) Group specification
81
H
to A0
H
: All stations in group No.1 to 32
(Setting is available when the execution type is set to "0: No
arrival confirmation" in (S1)+0.)
(3) All stations
FF
H
: All stations of the target network No. (Except the own
station)
(Setting is available when the execution type is set to "0: With
arrival confirmation" in (S1)+0.)
To specify a group or all stations, set "0000
H
" or "03FF
H
" for Target
station's CPU type (S1+3). (
Section 9.2.2 (3) When executing
a link dedicated instruction to a Multiple CPU system by specifying a
group or all stations)
1 to 120
81
H
to A0
H
FF
H
User
(S1)+6
—
Unused
0
User
(S1)+7
Number of resends
1) For instruction execution
Specify the number of times the instruction is to be resent when
it is not completed within the monitoring time specified in (S1)+8.
(Setting is available when the execution type is set to "1: With
arrival confirmation" in (S1)+0.)
0 to 15
User
2) At instruction completion
The number of resends executed (result) is stored. (Setting is
valid when the execution type is set to "1: With arrival
confirmation" in (S1)+0.)
—
System
(S1)+8
Arrival monitoring
time
Specify the monitoring time required for instruction completion.
(Setting is available when the execution type is set to "1: With arrival
confirmation" in (S1)+0.)
If an instruction is not completed within this time, it will be resent the
number of times specified in (S1)+7.
0: 10 seconds
1 to 32767: 1 to 32767 seconds
0 to 32767
User
(S1)+9
Write data length
*3
Specify the write data size of (S2) to (S2)+n.
When the target station is QCPU: 1 to 8192 words
When the target station is QnACPU: 1 to 480 words
When specifying 961 words or more, use channel 9 or 10 for the own
station.
1 to 8192
(1 to 960 when the
own station is a
safety CPU)
User
(S1)+10
—
Unused
0
User
(S1)+11
Clock set flag
*4
The valid or invalid status of the data in the area starting from (S1)+12
is stored.
0: Invalid
1: Valid
—
System
Table 9.17 Control data (Continued)
Device
Item
Setting data
Setting range
Setting
side
*1
Group No.1 81
H
Group No.2 82
H
Group No.32 A0
H
Содержание QJ71GP21-SX